INSTALLATION AND OPERATOR’S MANUAL SL375 THRU SL7175 OIL FIRED CAST IRON BOILERS Keep these instructions with the boiler at all times fo
10 VENTING Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe
11 Evidence of potential or existing chimney damage should be determined by visual inspection of the chimney and liner. Exterior indicators such as
12 With the burner operating, use a draft gauge to adjust the regulator to the proper setting (see instructions enclosed with draft gauge to adjust t
13 3. COMBINATION AIR INTAKE/VENT SYSTEM The vent system consists of 10, 15, or 20 foot lengths of 5” single wall flexible sta
14 The purpose of the damper is to act as a vacuum breaker in the event of a blockage in the air intake. NOTE: The balance weight of the vacuum rel
15DIRECT VENT OIL BURNERS Riello Burners All Riello direct vent burners are shipped with the nozzle for the SLD375 installed. A separate nozzle is
16 Oil Tank and Piping Oil tanks and piping should be installed in accordance with the National Board of Fire Underwriters and local codes. Connect
19Swing Door Opening the Door 1. Turn off power to boiler. 2. Allow boiler to cool down. 3. Unplug the burner power cable at factory-supplied bur
2 Be Aware of Hazard Definitions Denotes presence of a hazard which, if ignored, will result in severe personal injury, death or property damage Dang
20 Carlin 90200A Temperature Control 1. The Carlin 90200A temperature control functions as a high limit only. Start-Up Warning…Use only … No. 2 f
212. Direct vented – Take a draft reading from the inspection port of the boiler. This over-fire reading will be a positive pressure. Approximate
22 1. High limit control - Remove the temperature control cover as needed and note temperature setting. With the burner running reduce the high lim
232. Clean nozzle assembly and all air handling parts. 3. Check spacing and condition of ignition electrodes. Clean and replace as required. 4. N
24 Trouble Shooting Guide Burner Will Not Start Thermostat SetAbove RoomTemperatureHigh Limit Set onAquastat to 180Deg. Min.110 Volts betweenL1 and
25Burner Goes Off On Safety Oil Tank FullBleed Oil LinesOil Flows FreelyAir in Oil LinesPump Pressureto Burner Spec.SparkEstablishedNozzle CleanMatc
26 Item Qty. Description SL375 SL4100 SL5215 SL6150 SL6175 1 1 Riello F-5 Oil Burner 541151 541147 541148 541149 N/A 1
27Solaia Residential Cast Iron Boiler Warranty First Year Limited Warranty for Solaia Residential Cast Iron Water Boilers Boyertown Furnace warrants
28 Installation and Service Check List Boiler Model: _______________________ Serial No.: ____________________ Install
29 -----------------Cut and Return This Form or register online at www.boyertownfurnace.com----------------- W
3Table of Contents Ratings and Data………………………………………………………………………4 Clearances……………………………………………………………………...5 Ventilation and Combustion A
32
4 Ratings and Data Boiler Model No. SL375 SLD375 SL4100 SLD4100 SL5125 SLD5125 SL6150 SL7175 Firing Rate - #2 Fuel 0.75 0.75 1.00 1.
5Installation Clearances Boilers in rooms shall be installed with the clearances from combustible materials not less than indic
6 hundred (100) square inches. These openings must freely communicate with the interior areas having adequate infiltration from the outside. When
7the crated boiler to the carrier in good condition. ANY CLAIMS FOR DAMAGE OR SHORTAGE IN SHIPMENT MUST BE FILED IMMEDIATELY against the carrier by
8 Jacket installation 1. Open Cabinet Parts Box Check for damages. Damage claims must be filed immediately with carrier. 2. Install the (4) 3/4” O
9 System Piping Important… INSTALLATION MUST BE PERFORMED BY TECHNICALLY QUALIFIED SERVICEMEN SOLAIA BOILERS HAVE A MAXIMUM OPERATING PRESSURE OF